CAFO ISSUED 5/17/00 ASSESSING A PENALTY OF $46,750. RESPONDENT FAILED TO PROPERLY DISPOSE OF PCB-CONTAIMINATED OIL IN AN INCINERATOR WHICH COMPLIES WITH 40 C.F.R. SECTION 761.70. RESPONDENT FAILED TO PROVIDE A STORAGE AREA WITH ADEQUATE ROOF, WALLS, AND FLOORING WITH THE CONTINUOUS SIX-INCH CURBING FOR THE LEAKING PCB-CONTAMINATED TRANSFORMERS AS REQUIRED BY 40 C.F.R. 761.65(B)(1). RESPONDENT FAILED TO MARKED THE STORAGE AREA WHERE THE LEAKING PCB-CONTAMINATED TRANSFORMERS WERE STORED FOR DISPOSAL, WITH THE APPROPRIATE PCB LABELING AS REQUIRED BY 40 C.F.R. SECTION 761.65(C)(5). RESPONDENT FAILED TO PERFORM MONTHLY CHECKS FOR LEAKS AT LEAST ONCE EVERY 30 DAYS ON THE PCB-CONTAMINATED TRANS- FORMERS, AS REQUIRED BY 40 C.F.R. SECTION 761.65(C)(5). RESPONDENT FAILED TO DATE WHEN THE PCB-CONTAMINATED TRANS- FORMERS WERE REMOVED FROM SERVICE AND PLACED IN STORAGE FOR DISPOSAL, AS REQUIRED BY 40 C.F.R. SECTION 761.65(C)(8). REDS NO: 2000 032 232 286 587