← EPA enforcement cases

THERMO FLUIDS INC

Administrative - Formal · FY2021 · — · Final Order With Penalty · 3602817121

—
Penalty
—
Cost recovery
—
Compliance action

Case

Case Number
10-2021-0215
Type
Administrative - Formal
Lead
EPA
Outcome
Final Order With Penalty
Multimedia
—
Self-disclosure
N

Defendants (2)

Summary

On April 5, 2022, EPA Region 10 filed an expedited settlement agreement resolving violations of the Clean Water Act by Thermo Fluids, Inc. (TFI), located in White City, Oregon. TFI operates a used oil transporting, marketing, and processing operation that includes storage tank farm and a loading/unloading dock. An EPA spill prevention, control and countermeasure (SPCC) inspection on October 3, 2018, determined TFI lacked the following: 1) tank gauges on all tanks as prescribed in the SPCC plan, 2) adequate secondary containment for its sludge-bin and on the floor of TFI?s box truck, 3) SPCC-prescribed response equipment being on-site and 4) the SPCC Plan describing adequate response details. In addition, 5) SP-001 tank inspection were not conducted as previously prescribed and the SPCC Plan did not prescribe a schedule for future internal inspections. The Facility's fuel tanks have storage capacity of approximately 260,000 gallons and is connected via about 5,000 feet of roadside ditches to wetlands and the Rogue River. The Rogue River is a major recreational water body, and it supports major salmon species and wildlife habitats. TFI has spent an estimated $40,000 on the following complying actions, including: 1) repairs to box-truck oil containment, 2) tank gauge and high level alarm installation, 3) modifications to the vacuum waste pit, and 4) updates to the SPCC Plan. In addition, Thermo Fluids, Inc. paid a penalty of $2,500 for the SPCC regulatory violation

Source

Authoritative
EPA ECHO
Machine
JSON-LD · Markdown