Gamewell-FCI Recalls to Upgrade Software Used with Fire Alarm System Control Boards

CPSC Recall1 injuries · 2007-01-31 · 07526

Hazards

Incoming and outgoing messages to and from the control board can interfere with each other, preventing it from sending a message to the command center in the event of fire.

Recall

Number
07526
Date
2007-01-31
Injuries reported
1

Products

Names
Gamewell-FCI Electronic Control Boards by Honeywell

Companies

Manufacturer(s)
Gamewell-FCI, of Northford, Conn.
Retailer(s)
Authorized distributors nationwide from October 2005 through September 2006. Authorized distributors resell and install loop control boards for commercial end users in facilities such as hotels and office buildings.
Country of manufacture
United States

Description

The software upgrade involves Gamewell-FCI model ILI-MB-E3 and ILI-S-E3 loop control boards. These boards are components of the Gamewell-FCI E3 Series fire alarm system. They provide the signaling line circuits and display information for the system.