# Electrocution, electric shock at Milestone Electric
> OSHA SIR `2025088260` · 8/19/2025 · GRAND PRAIRIE, TEXAS
## Severity
- **1 hospitalization**
- **Body part:** BODY SYSTEMS
- **Nature of injury:** Electrocution, electric shock
## Cause
- **Event:** Indirect exposure to electricity  unspecified
- **Source:** Electrical wiring building or machine
- **Secondary source:** Pipes, tubes  metal
## Employer
- **Name:** Milestone Electric
- **Location:** 4221 Forest Edge Dr, GRAND PRAIRIE, TEXAS, 75052
- **NAICS:** 238210
- **Jurisdiction:** 1
## Narrative

An employee was brazing copper lines together on a new air conditioning unit close to an access point in a brick wall, The two wires ran horizontally and copper tubing ran vertically. The heat from the brazing heated up the copper tubing. A wire was touching the copper tubing, causing the wire jacket to melt. The wire infused itself to the copper tubing, which energized the copper pipe. The employee was using a wet towel to cool down the copper tubing when he was electrically shocked, resulting in hospitalization.

---